D SERIES FILL STATIONS

SKU: e8be183574a4 Category:

Description

System features :

  • Larger gauge panel for all features
  • Inlet and outlet 4″ gauges
  • Safety air shut off valve when door is open
  • Third party tested
  • Front door steel plate
  • Operator protection

 

D SERIES FILL STATION STANDARD FEATURES :

  • The D series SCBA recharging system is a free standing and complete filling/de-fragmentation station for 2216/3000 or 4500 psig cylinders. The SCBA refilling station is of a fully enclosed design to contain a SCBA or SCUBA cylinder failure or ruptured fill hose.
  • The Jordair D series fill stations are one of the safest the filling stations offered in Canada for the containment and recharging of SCBA cylinders.
  • A fully enclosed SCBA containment system that encloses both the SCBA cylinders and the filling hoses with a
    tilting front access door. The door must be closed and locked before SCBA cylinders can be recharged.
  • A toggle activated valve stops air flow to the filling points when the door is opened.
  • The front access door is held in the closed position by a spring loaded pin type door lock.
  • Heavy wall schedule 80 steel 8” pipe used to contain the SCBA cylinders within the recharge station.
  • Anti-abrasion collars and liners in the SCBA containment sleeves to protect the exterior of the SCBA cylinders
    from abrasion damage during the filling process.
  • 6000 psig inlet shut off valve to isolate the recharging station from the compressor and air storage cylinders.
  • One anodised aluminum, self-venting and adjustable regulator with operating pressures from 0 to 6,000-PSIG
    inlets and 0 to 6,000-PSIG outlet pressures.
  • Self-venting regulator comes complete with 4” inlet and discharge pressure gauges; gauges are rated for 7500 psig. Gauges read in both PSI and kPa.
  • 2½” pressure gauges for 2216/3000 or 4500 psig filling, installed for each fill outlet to indicate SCBA recharge
    pressure. Gauges read in both PSI & kPa.
  • Panel mounted SCBA cylinder shut off valves for 2216/3000 or 4500 PSIG fill positions.
  • SCBA recharge assemblies are supplied for 2216/3000 or 4500 psig filling.
  • A CRN certified safety relief valve is set for 2400/3200 or 4700 psig to protect the filling of the 2216/3000 or 4500 psig SCBA or SCUBA cylinders.
  • The SCBA 4500 PSIG cylinder fill hose assemblies will only recharge the high-pressure 4.5 SCBA cylinders. If a 2216 SCBA cylinder is accidentally connected the 4500 PSIG filling hose the filling adaptor will automatically vent to atmosphere.
  • All recharge hose assemblies are equipped with restriction orifices set to the CSA Z94.4 rate of 300 psig per
    minute, to control filling speed. When a cascade system is used, this prevents rapid cylinder expansion and
    significant pressure drop due to the compression heat created during a rapid refilling situation.
  • All pressure piping conforms to ASME code B31.1 and B31.3

 

NFPA 1901 CERTIFIED REGULATOR CONTROLLED FILL STATION – SLIDING DOOR
MODEL NO. OF FILL
POINTS
FILL TYPE FILL PRESSURE WEIGHT SIZE (CM)
H x D x W
J-FFS-D2-2 2 SCBA 2216/3000 PSIG 650 KG 175 x 86 x 97
J-FFS-D2-4 2 SCBA 4500 PSIG 650 KG 175 x 86 x 97
J-FFS-D3-2 3 SCBA 2216/3000 PSIG 660 KG 175 x 86 x 97
J-FFS-D3-4 3 SCBA 4500 PSIG 660 KG 175 x 86 x 97
J-FFS-D4-2 4 SCBA 2216/3000 PSIG 670 KG 175 x 86 x 97
J-FFS-D4-4 4 SCBA 4500 PSIG 670 KG 175 x 86 x 97
J-FFS-D6-2 6 SCBA 2216/3000 PSIG 700 KG 175 x 86 x 125
J-FFS-D6-4 6 SCBA 4500 PSIG 700 KG 175 x 86 x 125
J-FFS-D8-2 8 SCBA 2216/3000 PSIG 720 KG 175 x 86 x 125
J-FFS-D8-4 8 SCBA 4500 PSIG 720 KG 175 x 86 x 125
J-FFS-D10-2 10 SCBA 2216/3000 PSIG 830 KG 175 x 86 x 125
J-FFS-D10-4 10 SCBA 4500 PSIG 830 KG 175 x 86 x 125
J-FFS-D12-2 12 SCBA 2216/3000 PSIG 850 KG 175 x 86 x 125
J-FFS-D12-4 12 SCBA 4500 PSIG 850 KG 175 x 86 x 125